CFD Analsis Report for Lotte PJT in RUSSIA

Слайд 2

Drawing Design

0.7m

Top view

wall height 3m

Side view

Drawing Design 0.7m Top view wall height 3m Side view

Слайд 3

CFD 3D modeling

Wall height 3m

Top view

Iso view

CFD Analysis Condition
Product : Multi

CFD 3D modeling Wall height 3m Top view Iso view CFD Analysis

Operation ratio : 100%
Air temp. : 33℃
Roof wall height : 3m
Support height : 0.7m
CFD Analysis Program : FLUENT 13.0.0, GAMBIT 2.4.6
Viscous model : k-e standard model
Mesh : 6,791,555 hexahedral mesh

Mesh

Слайд 4

Temp [℃]

CFD Result

Pattern of discharge flow

Temp. contour on heat exchanger

Below 43℃

It is

Temp [℃] CFD Result Pattern of discharge flow Temp. contour on heat
shown that avg. Temp. of heat exchanger is distributed from 34℃ to 49℃ It seems that normal operation of AC product could be possible in these conditions.

Air temp. 33℃

Temp. contour on surface (h=1.5m)

Vel [m/s]

Temp. contour on surface

Velocity contour on surface

No recirculation

No recirculation