Operation Manual of Temperature. Control Box

Слайд 2

Operation panel instructions:

Actual temperature

Setting temperature

LED
Running state

KEY
Input key

Power switch

Lock position

Handle position

Alarm

Operation panel instructions: Actual temperature Setting temperature LED Running state KEY Input
description:
Thermocouple offline
Thermocouple connected reversely
Heater is disconnected
Silicon controlled breakdown

PV line is designed to be a four-digit nixie tube. In normal condition, it shows temperature of control target and in event of alarm, it shows malfunction code:

SP line is designed to be a four-digit nixie tube. In normal condition, it shows setting temperature:

Three indicators are soft start indicator, automatic operation indicator and manual indicator from left to right.

After initial power on, system enters soft start status. Dehumidify heating ring. Output power and operation time of soft start can be set up by menu. When soft start, this indicator flashes.

When system enter automatic constant temperature operation status, this indicator flashes.

When system enters manual operation status, this indicator flashes

PV

SP

SOFT

AUTO

MANU

E-01: Temp over
E-02: TC open
E-03: TC reverse
E-04: Heater open
E-05: Triac latch

Thermocouple is offline or no thermocouple is connected

Reverse connection of thermoelectricity polarity

E- 03

E- 02

Temperature out of range

E- 01

Setting temperature is 200 ℃

Setting temperature is 200 ℉

c200

F200

Heating ring is disconnected or no heating ring

Silicon controlled breakdown and short circuit

E- 04

E- 05

Thermocouple short circuit

E- 06

SENRITEC

Hot runner systens

Слайд 3

When system powers on and passes self-inspection, it enters operation status and

When system powers on and passes self-inspection, it enters operation status and
displays setup temperature and actual temperature:

How to set up temperature

200

c 200

201

c 201

200

c 200

Single press

Single press

Setup temperature increases by one degree with each press

Setup temperature decreases by one degree with each press

200

c 200

200

c 215

200

c 198

Long press

Long press

Setup temperature increases continuously, 5 degree in every second

Setup temperature decreases continuously, 5 degrees in every second

Single press

tens digit of setup temperature starts to flash

200

c 200

210

c 210

200

c 200

Single press

Single press

Setup temperature increases 10 degree by each press

Setup temperature decreases 10 by each press

200

c 200

280

c 280

120

c 120

Long press

Long press

Setup temperature increases continuously, 50 degree in every second

Setup temperature decreases continuously, 50 degrees in every second

Single press

Hundreds digit of setup temperature starts to flash

200

c 200

300

c 300

200

c 200

Single press

Single press

Setup temperature increases 100 degree by each press

Setup temperature decreases 100 degree by each press

200

c 200

450

c 450

000

c 000

Long press

Long press

Setup temperature increases continuously, 500 degree in every second

Setup temperature decreases continuously, 500 degrees in every second

Single press

Setup temperature has no flash digit

After parameter setting, you can press both Next key and Function key to store data quickly, or if there is no other press within 3 seconds, system data will be saved in EEPROM until the next time parameter is modified by user. Maximum setup temperature is 450℃.

200

c 200

Слайд 4

200

u 65

It shows percentage of manual output power, 99% at maximum and

200 u 65 It shows percentage of manual output power, 99% at
0% at minimum.

It shows current actual status. It may be actual temperature or alarm code.

Operation parameter monitoring

200

c 200

200

u50

200

n04.1

Single press

Single press

The lower line shows current output power percentage

The lower line shows current load current value

Status transition and display

After power on the controller, if initial target temperature is lower than 100 and it is in soft start mode, then system enters soft start mode automatically. If system is in soft start mode after starting up, flashes in every second. Soft start time and output power can be set up in the menu.

When soft start is over, it enters automatic operation mode and flashes in every second. After system power on, if it is detected that target value is higher than 100 degree or soft start mode is off, then it enters automatic operation mode.

In automatic operation status, long press to enter manual state.
In manual status, long press to return to automatic operation state.
In manual operation status, flashes in every second.
In manual operation status, SV screen shows manual output power, SP shows current state. Method of manual output power is the same as temperature setup .

200

u 65

It shows percentage of manual output power, 99% at maximum and 0% at minimum.

It shows current actual status. It may be actual temperature or alarm code.

* * * * *

* * * * *

Слайд 5

Function parameter settings

Function parameter settings include:
Regular function settings—temperature alarm

Function parameter settings Function parameter settings include: Regular function settings—temperature alarm upper
upper limit, temperature alarm lower limit, soft start power, soft start time, soft start switch
Advanced function settings-----thermocouple type, selection of centigrade and Fahrenheit, PID parameter, etc.

200

c 200

20

T-oU

-20

T-Lo

Long press

Enter temperature upper limit settings

Short press

Enter temperature lower limit settings

Set up by , method is the same as that of temperature settings

Set up by , method is the same as that of temperature settings

Enter advanced menu password settings

Long press

Long press

CodE

nc00

Long press When password settings are correct, long press this key will enter advanced settings menu.

Short press

Set up by , method is the same as that of temperature settings
CODE is 0—99, only when correct number is set up can you enter advanced menu.

Enter advanced menu settings zone

BACK

Enter parameter settings menu in automatic state

-on-

LOCK

Short press

Long press

-OFF

LOCK

Short press

Short press

Слайд 6

TC--

-J-

Short press

Short press

TC--

-K-

C--F

-C50

Short press

Enter selection zone of centigrade

TC-- -J- Short press Short press TC-- -K- C--F -C50 Short press
and Fahrenheit

C--F

-F60

Short press

Enter control method setup area

Long press

Long press

Setup menu of type J and type K thermocouple

Setup menu of centigrade and Fahrenheit

cont

SSR

cont

PWM

Short press

Enter time settings zone of soft start

Long press

Setup menu of zero crossing control and phase-shifting control mode

SOFT

t. 01

Set up by , setup method is the same as that of temperature settings.
Soft start is mainly for dehumidify heater. When mould is not used for a long time, please select soft start mode. PWM soft start mode is the best. Setup time shall not be less than 60 minutes. If the mould is always in use, set up short time, e.g., 2 minutes.

Short press

Long press

SOFT

P 10

Set up by , setup method is the same as that of temperature settings.
Soft start is mainly for dehumidify heater. When mould is not used for a long time, please select soft start mode. PWM soft start mode is the best. Setup power shall not exceed 10%.

Long press

Enter setup zone of soft start power

Short press

Short press

Short press

Short press

Short press

Слайд 7

20

-KP-

Set up by通过 , setup method is the same as that of

20 -KP- Set up by通过 , setup method is the same as
temperature settings.
KP value is scale-up factor. When AP is ON, temperature controller will calculate and save this value based on heater features automatically. Do not change this number generally. Only in special circumstances will technicians be allowed to change this number.

Long press

60

-Ki-

Short press

Enter parameter I setup zone of PID controller

Set up by setup method is the same as that of temperature settings.
Ki number if integral scale-up factor. When AP is ON, temperature controller will calculate and save this value based on heater features automatically. Do not change this number generally. Only in special circumstances will technicians be allowed to change this number.

15

-Kd-

Short press

Enter D parameter setup zone of PID controller

Set up by , setup method is the same as that of temperature settings. Kd is differential scale-up factor. When AP is ON, temperature controller will calculate and save this value based on heater features automatically. Do not change this number generally. Only in special circumstances will technicians be allowed to change this number.

Long press

Long press

-AP-

_ON

Short press

Enter parameter automatic adjustment switch setup zone

Short press

Short press

-AP-

_OFF

Long press

Short press

Generally, AP is ON.
When AP is ON, controller tests heater functions automatically during each power on and temperature rise. When temperature controller gets accurate heater parameter, it performs accurate control.
When AP is OFF, controller will not test heater function, but withdraw parameter from previous record. If temperature controller controls the same heating ring, it is stable.