For safety door bypass relay, we should separate bypass and feedback to PLC

Слайд 2

NO.2

What’s the special function for this encoder ,
actually ,there is no need

NO.2 What’s the special function for this encoder , actually ,there is
for this encoder in PJC18-227

Слайд 3

NO.3

Please change the pin assign for oriental motor driver , for the

NO.3 Please change the pin assign for oriental motor driver , for
one we use, pin 1/2/13/14 is only used for pulse input ,
We should start input from IN4 (PIN3) ,please check use manual

Слайд 4

NO.4

We ‘d better assign 0v com for driver input signal ,for all

NO.4 We ‘d better assign 0v com for driver input signal ,for
the driver ,in case we use input signal

Слайд 5

NO.5

Please add terminals to wire for the camera light

NO.5 Please add terminals to wire for the camera light

Слайд 6

NO.6

For the signal to other machine ,can’t connect with our power system

NO.6 For the signal to other machine ,can’t connect with our power
,just control their signal connect/cut